As part of the commissioning process for gaseous fire suppression systems, room integrity door fan testing is mandatory under AS ISO 14520 and NFPA 2001 along with the recording of the extinguishing systems baseline data for future testing and maintenance records.
DIS Fire Systems have multiple trained operators in all states throughout Australia who can review the system installation, the suitability of the enclosure to maintain the extinguishing agent, requirements for pressure relief venting and that the system will maintain the extinguishing agent for the specified hold time.
As part of the ongoing maintenance requirements for gaseous fire suppression systems, AS 1851-2012 requires a room integrity door fan test be performed every twelve (12) months as part of the annual servicing of the system, with the test results recorded and measured against the original system design and baseline data provided at the time of installation.
On older installations this baseline data may not exist and DIS Fire Systems can review the installed system, taking into account the following: